Package Summary  Diesel Engine  |  Generator 
Emissions & Abatement  |  Switchgears
Service Records  |  Pictures  |  Specs and Manuals


Service and Maintenance Records

  

Unit #

Date

Mach. Hours

Fluid

Quantity

G-1E

6-9-01

 

Start eng at idle, warmed up 20 min, ran at rated speed 30 min.

 

 

6-16-01

 

Started eng at idle for warm up

 

 

7-4-01

 

Oil

5gal

 

7-5-01

 

Oil

5gal

 

7-11-01

 

1st valve adjust

 

 

7-17-01

19

Oil & filter chg

 

 

7-27-01

 

Antifreeze

30

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G- 1W

7-4-01

 

Eng. Oil

5 gal

 

7-5-01

 

Oil

5 gal

 

8-27-01

 

Antifreeze

30

 

3-19-03

234

Adjust Valve

 

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-2E

6-9-01

 

Started up Gen at idle for 20 min, ran at rated speed for 30 min.

 

 

6-10-01

 

Started up Gen at idle for warm up

 

 

7-4-01

 

Eng oil

5gal

 

7-5-01

 

Oil

2.5gal

 

7-11-01

 

Adj. valves & Eng for 1st time

 

 

7-19-01

212hrs

Oil & filter chg

 

 

8-27-01

 

Antifreeze

30

 

1-27-04

 

Engine auto shut down/ operate 1 hr

 

 

1-28-01

 

Ran engine for trouble shoot/ operate 1 hr

 

 

1-30-04

 

Broken injector of valve cyl 12

 

 

wonum

description

work type

status

WO60876

MLD, Technicians, G-2E, Exhaust Gas Temperature Sensor Calibration

The technicians discovered that the temperature sensor calibration was correct. The Sinox computer was not reading the input from the sensor correctly. The technicians swapped Sinox computers with one of the dead units.

NFCM

MECOMP

WO60910

Urea System Starting at 624 degrees, should start at 580 degrees

Adjusted urea starting temp.

NFCM

MECOMP

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-2W

8-20-01

 

Replaced generator vibration

 

 

8-27-01

 

Antifreeze

30

 

9-13-01

49

Antifreeze

Added 5gal

 

10-1-01

49

Replaced cyl. liners

 

 

11-19-01

57

Oil

5gal

 

wonum

description

work type

status

WO60911

Starting Battery Low Alarm Locked in on Control System, Voltage Normal.

We found G-2W with no alarms. Voltage at battery bank was over 28v, nearly the same as indicated on charger unit. This voltage was typical as compared to other units. G-2W was started and allowed to run long enough to test the sinox (urea) system.

NFCM

PLREV

 

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-3W

8-27-01

 

Antifreeze

30gal

 

9-13-01

81

Antifreeze

5gal

 

11-19-01

89

Motor oil

5gal

 

12-12-01

93

Motor oil

5gal

 

wonum

description

work type

status

W036294

Left block heater B/O

Wires burned up from loose connection

NFCM

CLOSE

WO41456

Engine block heater not cycling

Stole thermostat from extra heater on shelf, ordered and received 2 spares. Heater on solid, found block extremely hot. Supply breaker open.

Remove old thermostat and install new.

BRKDN

CLOSE

WO42200

Fuel day tank not filling

Trouble shot system, Fles conduit was broken, grounding out and burnt wire in two. Replaced wiring and tested EQ. Control panel on top of day tank indicated that fuel solenoids are electrical;

Check solenoid operation.

NFCM

CLOSE

 

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-4W

7-4-01

 

Engine oil

10gal

 

8-27-01

 

Antifreeze

30gal

 

9-12-01

85

Motor oil

5gal

 

9-13-01

85

Antifreeze

5

 

2-26-03

 

Motor oil

2.5gal

 

wonum

description

work type

status

WO51603

Replace block heater hose.

Hose is leaking and needs to be replaced. This is the hose between the block and the block heater.

NFCM

CLOSE

WO52832

Fuel leak at day tank fill valve settings.

Note from craft: replaced a leaking o-rink on the solenoid valve. Electricians noticed the leak and isolated it. Operator Pat Kelley spent a lot of time looking but couldn’t pin point where the leak is at. Possibly at the solenoid valve.

NFCM

CLOSE

WO44518

G4W- North block heater, replaced, new wire.

NFCM

CLOSE

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-5W

7-4-01

 

Eng. Oil

2.5gal

 

7-5-01

 

Oil

5gal

 

7-28-01

 

Antifreeze

30gal

 

9-12-01

111

Motor oil

5gal

 

9-13-01

111

Antifreeze

5gal

 

wonum

description

work type

status

WO36373

Battery charger all out of whack

On 1-15-04 we pushed the equalize button on the battery charger and the float charge was corrected.

Trouble shoot and repair if possible

Replace if repair isn’t possible

NFCM

CLOSE

WO53853

Day tank leaking from inlet piping.

Note from craft 9-27-05: Replaced bad o-ring on solenoid valve. Operator says this is a serious leak and needs immediate attention.

NFCM

CLOSE

WO61879

South Block Heater Boiling and Not Shutting Off

Lowered T-Stat temp.

NFCM

PLREV

 

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-6W

6-29-01

 

Oil

5gal

 

7-4-01

 

Oil

10gal

 

8-27-01

 

Antifreeze

30gal

 

9-13-01

113

Antifreeze

5gal

 

11-19-01

118

Oil

5gal

 

wonum

description

work type

status

WO44518

G6W- North block heater, new wire

NFCM

CLOSE

 

 

Unit #

Date

Mach. Hours

Fluid

Quantity

G-7W

7-4-01

 

Eng oil

2.5gal

 

7-5-01

 

Oil

5gal

 

8-27-01

 

Antifreeze

30gal

 

9-12-01

112

Motor oil

5gal

 

9-13-01

112

Antifreeze

2gal

 

11-19-01

120

Oil

5gal

 

wonum

description

work type

status

WO36291

House heater motor froze up

Installed new motor 2-18-04

Remove heater/repair motor

NFCM

CLOSE

WO47906

Non Working Block Heater

Required the replacement of the thermostat and some of the heater wiring.

BRKDN

CLOSE

WO44518

G7W- South block heater, replaced, new wire

NFCM

CLOSE

 

 

 

Unit #